Steam boiler in container solution. 20 feet.
The boiler is in very good condition,
Use <1000h then new,
Has only run on diesel, deionized boiler water and it worked the last time it was used in 2020. Started in the summer of 2021.
Inspected September 2017.
There is a known fault and that is that the actuator for one of the automatic valves at start-up does not work automatically as intended but there is a manual knob that you can use at start-up instead according to the instructions that come with it.
When connecting and starting up, a check and service should be done.
Purchased: end of 2014. New price approximately SEK 850,000
20 foot container with some protrusions here and there.
About measurements.
6.10 m + protrusion 30 cm x 2.45 m + 20 cm x Height 2.60 m + 55 cm chimney.
PS: The owners have access to help with lifting assistance / loading.
We want collection to take place no later than 20/1 -22, but preferably earlier.
Screening will take place on Tuesday 7/11 at 14.00.
Registration must be handled by the responsible administrator no later than Monday 6/11 at 15.00.
Registration is made to pelle.holmstrom@ps.se
Mark registration with contact person / persons & mobile number and Display steam boiler.
Other information taken from the quote. See also attached appendix.
Boiler unit - Type: Steam generator boiler - Type DT-1000/1000 Low NOx.
General description: Compact water pipe steam boiler made of wound pipe loops and complete with burner. Insulated and covered with stainless steel.
Steam production: 900 kg / h nominal (saturated) - based on feed water @ 55 ° C (min. 50 ° C / max. 90 ° C)
Net heat capacity: 641 kW nominal - equal to 551 Mcal / h
Nominal working pressure: 22.0 bar pressure gauge (setpoint for working pressure regulator) | Steam temperature: 220 ° C
Design pressure: 26.0 bar pressure gauge - safety valve setpoint
Voltage: 3 x 400 Volt + Neutral + Earth | Frequency: = 50 Hz (other values on special request)
Efficiency and emission: 88 - 90% based on LCV of 42300 kJ / kg oil - depending on actual loads and variations.
Steam dryness: 95-97% nominal and up to 98-99% weight. steam dryer or steam buffer arrangement fitted.
Environmental design (low NOx): Combustion chamber load below 1.0 MW / m³ - for optimal utilization of low-NOx burners.
Burner - Monoblock Type: Light fuel oil - quality corresponds to European (EU) normal industrial fuel standards. (mounted & wired) Consumption: 63 kg / h oil - based on the above caloric value (LCV).
General specifications:
In addition to the above, the boiler unit includes the following positions, mounted and connected:
Feed water pump including electric motor - mounted and connected to control panel.
- Steam valve, strainer, shut-off valves and other fittings.
- Safety equipment and high pressure control with switch, alarm and safety blowout.
- Pressure gauge, thermometer, sight glass, instrument displays and other local displays.
- Control panel in class IP54 for fully automatic operation including start-up, operation,
standby mode, stop and close. To ensure a stable vapor pressure, it is at the setpoint.